Holby Monitor

General Description
The HolbyMonitor tracks domestic hot water temperatures continuously.
The HolbyMonitor continuously monitors and displays the cold, hot and tempered hot water temperatures and transmits an ALERT message if any water temperature exceeds custom-selected temperature limits. ALERT messaging can be sent to multiple recipients via text message and/or email.
Monitoring the tempering valve outlet water temperature is important. However, monitoring the cold and hot water inlet temperatures provides valuable information about the overall domestic hot water system. This information enables detection of a failed hot water recirculation pump, overheated cold water lines, and failed boilers and hot water heaters.
The basic system includes two devices; a Base Station and at least one Temperature Transmitter (node). The node monitors the hot, cold and tempered water temperatures continuously and communicates wirelessly with the Base Station.
The Base Station monitors the information it receives from the node and compares the information to the custom-defined limits. If any limit is exceed an email and/or text message can be sent to the Primary Contact and Additional Contacts.
Quick start document
Setup Base Station
Box Contains:


Connect to the internet. We recommend a wired Ethernet connection plugged into the right side of the Base Station.
Optional Wi-Fi Connection: If the site does not have a wired connection available, the Base Station can connect to the internet using a 300Mbps Wireless-N USB Adapter with Antenna (sold separately) inserted into a USB slot on the right side of the Base Station. Go to the “Connect to Wi-Fi” section for details. A Wi-Fi connection would replace the need for an Ethernet cable. Note: Only secured Wi-Fi can be used.
Setup Node
Box Contains:


Install Node
The node can be wall-mounted or strapped to the Cold water supply pipe near the Holby Tempering Valve.
IMPORTANT: ALL SENSORS MUST HAVE DIRECT CONTACT WITH THE COPPER PIPES.
Secure the BLUE sensor to the COLD water supply pipe with a hose clamp, available from Holby Valve.
NOTE: Attach sensor between the Holby Tempering Valve and the point where the recirculating and cold water are mixed.
How to Login
Download Free App
Register Your Account
In the Register window, enter the following details, then tap Register Account.First Name | Required |
Last Name | Required |
Required. Alerts will be sent to this Email address. Note: this Email and Password is required to log into your HolbyMonitor account via the Holby App. If multiple users will be accessing the account via the App, you will need to share this Email address and Password. | |
Password | Required |
Verify Password | Required |
Notify All (Email) | Check box if you want all alerts to be sent to this Email address. |
Lack of Communication notify (Email) | Check box if you want alerts to be sent to this Email address in the event of a break in communication between the Base Station and Cloud. |
Phone | Re Required if cell phone number is to receive text message alerts from your HolbyMonitor quired |
Company | Building Ownership |
Address | Job site location |
Address 2 | Optional |
Ciy | Job site location |
State | Job site location |
Zip | Optional |
Country | Default is United States |
Time Zone | Select appropriate Time Zone. Default is America/Adak (Alaska) |
Owner | Currently only 00-0000 is available. Needs instruction here. |
Accept Terms | Required. Select checkbox. Click on Terms to view details. |
A window will pop up indicating your account has been created. Your email address must be validated in order to login. Check the email Inbox for validation email and respond.
Both email address and cell phone number must be validated in order to receive alert messages.
Sign In button is displayed at bottom.
Validate account: A validation text message and an email will be sent to the cell phone number and email address entered when you set up the account. Tap on link in text message to validate phone number, also click on link in email to validate email address.
Add base station to account – via smartphone
Enter the Base Station’s 16-digit MAC ID.
- The MAC ID is printed on the barcode label on the left side of the Base Station and on the shipping box
- Enter all alpha characters in lower-case format.
Add node to account – via smartphone
Enter the Node’s 16-digit MAC ID.
- The MAC ID is printed on the barcode label on the back of the Node, inside the battery compartment lid and on the shipping box.
- Enter all MAC ID alpha characters in lower-case.
Review and set alert limits – via smartphone
Setpoint | Default Setpoint | Description |
---|---|---|
Mixed Low Temp Alert Setpoint | 105 | Alert will be sent when Mixed temp falls below this setpoint. |
Mixed High Temp Alert Setpoint | 132 | Alert will be sent when Mixed temp exceeds this setpoint. |
Mixed Temp Shutdown Setpoint | 140 | If the Mixed temp exceeds this setpoint AND the Mixed Shutdown Enable box is checked, the solenoid on the Hot water supply pipe will be triggered to close and an alert will be sent. |
Mixed Shutdown Enable | Un-checked | Check box to allow this sensor unit to control shutdown. ONLY ONE SENSOR CAN BE ENABLED PER BASE STATION. |
Hot Low Temp Alert Setpoint | 130 | Alert will be sent when the Hot water temp falls below this setpoint. |
Sensor Unit Reset | Un-checked | Check box to reset the sensor unit on next reporting cycle. |
Base Station Reset | Un-checked | Check box to reset the Base Station on next reporting cycle. |
Connect to wi-fi – via base station
Enter the password for the selected wireless network.
- Use the arrow-keys to advance to the next character to be entered. NOTE: Enter all password alpha characters in the proper case.
- Use the numbered buttons as shown below. NOTE: The numbered buttons cycle through the number, capital letters and special characters.
- Press OK.
# | Caps | Special Characters |
---|---|---|
1 | !, ?, ‘, ~ | |
2 | A, B, C | a, b, c, @, ,, = |
3 | D, E, F | d, e, f, #, ., - |
4 | G, H, I | g, h, i, $, |, + |
5 | J, K, L | j, k, l, %, ;, : |
6 | M, N, O | m, n, o, ^, _ |
7 | P, Q, R, S | p, q, r, s, &, / |
8 | T, U, V | t, u, v, *, \ |
9 | W, X, Y, Z | w, x, y, z, (, {, [ |
0 | Space, ), }, ] |
Setpoint | Default Setpoint | Description |
---|---|---|
Mixed Low Temp Alert Setpoint | 105 | Alert will be sent when Mixed temp falls below this setpoint. |
Mixed High Temp Alert Setpoint | 132 | Alert will be sent when Mixed temp exceeds this setpoint. |
Mixed Temp Shutdown Setpoint | 140 | If the Mixed temp exceeds this setpoint AND the Mixed Shutdown Enable box is checked, the solenoid on the Hot water supply pipe will be triggered to close and an alert will be sent. |
Mixed Shutdown Enable | Un-checked | Check box to allow this sensor unit to control shutdown. ONLY ONE SENSOR CAN BE ENABLED PER BASE STATION. |
Hot Low Temp Alert Setpoint | 130 | Alert will be sent when the Hot water temp falls below this setpoint. |
Sensor Unit Reset | Un-checked | Check box to reset the sensor unit on next reporting cycle. |
Base Station Reset | Un-checked | Check box to reset the Base Station on next reporting cycle. |
Add additional contacts – via smartphone
Name | Required |
Required. Alerts will be sent to this Email address | |
Notify (Email) | Check box if you want alerts sent to this Email address. |
Phone | Required. Alerts will be send to this Cell Phone number. |
Notify (Cell Phone) | Check box if you want alerts texted to this Cell Phone number. |
Devices |
|